1. To copy to USB memory manually:
Attach the USB memory to TOP or press the [USB] button in the top menu on the RUN screen to open the USB menu.
After pressing the [Global Data] button, the [Log Upload/Alarm Upload] button will appear below.
Click [Alarm Upload], and the [Select Path] screen will appear, where you can set the save path for the alarm file. Clicking [OK] will start the upload process.
When complete, the alarm data will be saved in CSV format on the USB memory. The CSV file can be opened with Excel or a standard editor (like Notepad).
2. To copy automatically according to set conditions:
※ This function is supported from TOP Design Studio V1.4.10 and above.
Register an object (Image/Touch/Rectangle/Arithmetic, etc.) with an [Effects and Operation] page.
Set the [Operation] - [Special] - [System] - [Alarm CSV Export] and choose [USB] as the save location.
Whenever the set condition is met, alarm data is copied to the USB memory. The alarm data is stored as a CSV file by date. The file name format is [2019-07-04 (the date of the alarm data)_A01 (Group ID)_ALARM.CSV].
3. To copy an alarm file backed up on an SD card to a USB memory:
You can use the file explorer to copy alarm files backed up on the SD card to a USB memory, as shown in the diagram. Start the file explorer from the TOP main menu [File Browser], or on the TOP run screen by clicking the [Browser] button.
4. Mount the USB memory onto the TOP main unit.
Press the [Memory] button at the top left to switch to SD card mode.
In the SD card's [HMIAlarmBlock1 (block number)] folder, select the alarm files (.CSV). To select multiple files, press the [Select] button, then select each file you wish to copy in order. Press [Copy] to copy.
Press the [Memory] button again to switch to USB memory mode.
After selecting the folder to paste into, press the [Paste] button to complete the copying process.